APC UPS Monitoring - Useful OIDs
For APC UPS monitoring, here are some of the OIDs (Object Identifiers) you'll want to use. These OIDs definitely work with the APC AP9617 management card which plugs in the back of APC devices.
General UPS Monitoring Info
UPS Type .1.3.6.1.4.1.318.1.1.1.1.1.1.0
String containing UPS model, eg: Smart-UPS 1000
Battery Information
Battery capacity .1.3.6.1.4.1.318.1.1.1.2.2.1.0
Battery capacity as % of total
Battery temperature .1.3.6.1.4.1.318.1.1.1.2.2.2.0
Battery temperature in Celcius of Farenheit - depending on how UPS is configured
Battery runtime remain .1.3.6.1.4.1.318.1.1.1.2.2.3.0
Total battery runtime available based on current load.
Battery replace .1.3.6.1.4.1.318.1.1.1.2.2.4.0
If result = 2 then battery needs replacing (1 = ok)
UPS Input
Input voltage .1.3.6.1.4.1.318.1.1.1.3.2.1.0
Input voltage, to the UPS device
Input frequency .1.3.6.1.4.1.318.1.1.1.3.2.4.0
Input frequency in Hz
Reason for last transfer .1.3.6.1.4.1.318.1.1.1.3.2.5.0
String containing reason for last transfer to battery power
1 No events
2 High line voltage
3 Brownout
4 Loss of mains power
5 Small temporary power drop
6 Large temporary power drop
7 Small spike
8 Large spike
9 UPS self test
10 Excessive input voltage fluctuation
UPS Output
Output voltage .1.3.6.1.4.1.318.1.1.1.4.2.1.0
Output voltage from the UPS
Output frequency .1.3.6.1.4.1.318.1.1.1.4.2.2.0
Output frequency in Hz
Output load .1.3.6.1.4.1.318.1.1.1.4.2.3.0
Output load expressed as % of capacity
Output current .1.3.6.1.4.1.318.1.1.1.4.2.4.0
Output current in Amps
Diagnostics
Comms .1.3.6.1.4.1.318.1.1.1.8.1.0
Whether SNMP agent is communicating with UPS device 1 = yes, 2 = no
Last Self Test result .1.3.6.1.4.1.318.1.1.1.7.2.3.0
Result of last self test as text string. eg: pass or fail.
Last Self Test date .1.3.6.1.4.1.318.1.1.1.7.2.4.0
Date of last self test